Capacity compensation calculation
Example: The actual active power consumption P=550KW, the power factor before compensation is 0.70, and the power factor after compensation is required to reach 0.93,
According to the table, if the compensation factor is 0.625, the required compensation capacity is 550X0.625=343 (kvar)
In addition, the installation capacity of the complete set of devices needs to consider a capacity margin of about 1.2-1.4 times based on the fundamental compensation capacity.
Before compensation: 550 ÷ 0.70=785.7 (KVA), 800KVA transformer needs to be selected
After compensation: 550 ÷ 0.93=591.4 (KVA), only 630KVA transformer needs to be selected