Welcome to the official website of Guangdong  Dedi Mechanical And Electrical Equipment Co., Ltd!

 Tel:0758-6663288       E-mail:2823802733@qq.com

图片展示
图片展示

Structure and installation instructions of high-voltage reactive power compensation device

Author:广东德帝机电有限公司 Click: Time:2018-01-02 00:00:00

High voltage reactive power compensation devices are mainly used for reactive power compensation in three-phase power systems with power frequencies of 6kV, 10kV, and 35kV. They are used to adjust and balance grid voltage, improve power factor, reduce line losses, improve power quality, and fully utilize the efficiency of power generation and supply equipment.

Centralized compensation refers to the concentrated installation of capacitor banks on the busbars of the power transformation and distribution room, which can be put into operation at once when compensation is needed. The characteristic is that the compensation effect is poor. Due to the fixed capacity, it cannot accurately compensate, and can only compensate for the reactive power of the busbar and high-voltage lines, but the investment is relatively small and easy to maintain.

Structural characteristics

The device consists of a high-voltage switchgear (including high-voltage circuit breakers, isolation switches, current transformers, relay protection, measurement and indication parts, etc.), series reactors, zinc oxide lightning arresters and their recorders, discharge coils, isolation switches, grounding switches, high-voltage parallel capacitors and their dedicated fuses, post insulators, connecting busbars, fences, and galvanized steel structures.

2. The device adopts a dry type air-core reactor or a dry type iron core reactor connected to the neutral or power side of the device to limit the closing inrush current, suppress higher harmonics, and improve the network voltage waveform. Reactor parameter selection:

Suppress closing inrush current, with a reactance rate of generally 1%;

Suppress more than 5 harmonics, with a reactance rate of 4.5-6%;

Suppress more than 3 harmonics, with a reactance rate of 12-13%.

3. The zinc oxide lightning arrester is connected to the capacitor bank line in parallel to limit the operating overvoltage caused by switching the capacitor bank.

4. The discharge coil is connected to both ends of the capacitor in parallel. When the power supply of the capacitor bank is disconnected, the residual voltage at both ends of the capacitor can be reduced to 0.1 times the rated voltage or below 50V within 5 seconds.

5. The high-voltage fuse is connected in series with the capacitor. When 50-70% of the series components inside the capacitor are broken, the fuse acts to quickly remove the faulty capacitor from the capacitor bank, effectively preventing the fault from expanding.

6. According to the layout of the equipment (capacitors, reactors, etc.) configured in the device, it can be divided into sheet type, cabinet type, fence type, modular type, and collective type.

The chip frame structure refers to the components measured by the chip frame (including straight beams, crossbeams, and crosspieces), which are connected by a series of standard components such as bolts to form a capacitor bank framework. It is surrounded by mesh doors, and the device has the characteristics of low price and convenient transportation.

The cabinet structure is to install all the configured components on a structure similar to a high-voltage switchgear, and the cabinet door is made of steel plate or galvanized steel mesh. The device consists of three parts: reactor cabinet, discharge cabinet, and capacitor cabinet. The device has the characteristics of neat appearance and convenient installation.

The fence structure refers to the detachable mesh gate guardrail around equipment such as capacitor banks and reactors, with maintenance channels left between the fence and the equipment.

Dense type capacitors mainly use collective capacitors, which are installed on the cabinet frame in three groups of several capacitor units, one for each phase. Each component inside the capacitor unit is connected to an internal fuse in series. When individual components break down, other intact components discharge them, causing the fuse to melt, thereby disconnecting the damaged components and ensuring that the capacitor can still operate.

For devices with voltage levels of 7.10kV and below, the operating capacitor casing is directly grounded for use. When using star wiring, the neutral point should not be grounded.

For devices with voltage levels of 35kV and above, capacitors are installed on insulation platforms of corresponding voltage levels, which meet the insulation requirements of the device for enemies.

technical parameter

1) Compensation effect: After compensation, the power factor can reach 0.92.

2) High voltage power capacitors using advanced technology and full film dielectric have the characteristics of high reliability, long service life, small losses, low operating temperature rise, and also have outstanding characteristics such as high discharge starting voltage and good sealing performance.

3) Reasonable structural design, good thermal and dynamic stability. Equipped with high-voltage live display, electromagnetic lock, observation window, with forced locking function;

4) The device can operate for a long time under a steady-state overvoltage of 1.1 times the rated voltage.

5) The device can operate continuously under an overcurrent with a root mean square value not exceeding 1.3 times the rated current of the capacitor bank.

6) According to the needs of the system and users, the device can be controlled locally or in the main control room, centralized control, or automatic control.

7) The difference between the measured total capacity of the entire capacitor bank and the total rated value of each capacitor shall not exceed+10%~0, and the capacitance deviation of each phase shall not exceed 5%.

Protection method

The device adopts high-voltage spray type fuses or current limiting fuses as short-circuit protection for a single capacitor, ensuring the safe operation of the equipment.

The device adopts open delta voltage, voltage differential, and neutral unbalanced current protection as backup protection.

The device is also equipped with overvoltage, overcurrent, voltage loss, etc. as external protection for the device.

The device adopts a high-voltage circuit breaker without heavy breakdown to switch the capacitor bank, and is equipped with a suitable zinc oxide lightning arrester to limit the operating overvoltage generated when switching the capacitor bank.

图片展示

About | Product | Equipment |Case | News

图片展示

微信公众号

图片展示

微信小程序

CONTACT US


Tel:0758-6663288

Fax:0758-6663288-828

E-mail:2823802733@qq.com

Add:201, 2nd Floor, Building 8, Yingtian Zhigu Industrial Park, Pingfeng Expansion Zone, Guangdong Guangxi Cooperation Special Experimental Zone, Pingfeng Town, Fengkai County, Zhaoqing City, Guangdong Province

Copyright@ Guangdong  Dedi Mechanical And Electrical Equipment Co., Ltd  All Right Reserved       ICP: 粤ICP备15100755号-1            粤公网安备 44060602000701号

Copyright@ Guangdong  Dedi Mechanical And Electrical Equipment Co., Ltd  All Right Reserved       ICP: 粤ICP备15100755号-1            粤公网安备 44060602000701号

 

Service Center
Contacts
Qrcode
Top
Service Center
Contacts
热线电话
0758-6663288
上班时间
周一到周五
E-mail地址
2823802733@qq.com
Qrcode
Qrcode
扫码关注
Add WeChat friend to learn more about the product
Use Enterprise WeChat
"Scan" to join the group chat
Copy success!
Add WeChat friend to learn more about the product
I see.