Product Introduction
At present, power supply enterprises in various regions are equipped with an emergency power generation vehicle, which has been widely used in places such as emergency repair and disaster relief, power supply guarantee, and temporary power supply guarantee for important customer failures and power outages. However, after several years of use, some defects were discovered. 1. The installation of the emergency power supply connection device is troublesome, usually taking several hours to complete, seriously affecting the time for power recovery and wasting valuable time. 2. The emergency power supply access device is not standardized because the on-site electrical devices are diverse and may not necessarily be matched with the emergency power supply access system. It often needs to be modified before being connected, and the access point is not very reliable. 3. The switching device of the emergency power supply has some safety hazards and lacks corresponding protection, which affects the safe use of the emergency power supply vehicle. 4. The number of emergency power generation vehicles is small due to the cumbersome steps of connecting to client devices, heavy workload, and long working hours, making it difficult to meet the requirements of multi-point power supply.
In response to the above problems, Guangdong Shunde Dedi Electromechanical Equipment Co., Ltd. has developed a set of emergency power supply quick access device using existing electrical quick connector equipment and microcomputer intelligent relay protection technology.
Model Description

Application
It can be widely used in various types of main substations, and can be quickly connected to the emergency power supply on the low-voltage side of user specialized transformers or the low-voltage side of public transformers.
Referenced standards
GB/T 11918.1-2014 "General Requirements for Industrial Plugs, Sockets, and Couplers"
GB/T 7251.12-2013 "Low voltage switchgear and control equipment - Part 2"
GB/T 34989-2017 "Connector Safety Requirements and Tests"
technical specifications
1、 Environmental conditions for use:
Altitude: Altitude not exceeding 2000M
Environmental temperature: -30 ° C~+125 ° C
Relative humidity: When not plugged in, it is allowed to cause condensation of humidity within the unit due to changes in humidity. When plugged in, it is not affected by humidity.
Seismic resistance: The ground horizontal acceleration shall not exceed 0 3g, ground vertical acceleration 0.15g,
Installation location: inside the indoor switch cabinet or inside the outdoor box.
2、 The rated parameters of the panel sockets used for emergency access devices are as follows:
Rated current: 530 amperes/connection
Rated voltage: 1000V (AC)/1500V (DC)
Test voltage: 4500VAC
Short circuit current: 12KA/s 34KA/peak
Insulation resistance: > 500M Ω
Contact resistance: < 30 μ Ω
Sealing immersion test: constant pressure load cycling test (30 cycles in water without breakdown)
Connection material: T2 copper (630 ampere) silver plated
Shell material: High temperature resistant plastic material
Waterproof grade: IP67
Insertion and unplugging times: ≥ 5000 times
Vibration: 10-200Hz/15g
Contact type: strap connector
Working temperature: -30 ° C to+125 ° C
Structure length (mm): < 100
3、 Structural requirements:
The shell of the functional unit is made of metal material, and the surface is treated with electrostatic spray anti-corrosion. External reference dimensions L=600mm, W=200mm, H=300mm.
The functional units are expandable and can be flexibly expanded by multiple functional units to meet different capacity requirements depending on the required capacity.
The functional unit reserves copper bus terminals for easy connection to the low-voltage system.
The insulation components should have sufficient heat resistance, and the maximum temperature that can be reached under normal working conditions should not cause harmful damage to them.
After aging test, the insulation components should be placed at room temperature and relative humidity of 45% to 55% for no less than 24 hours. Use flame-retardant (flame retardant) or self-extinguishing insulation materials with sufficient mechanical strength.
Visually, the test sample should have no changes, that is, no surface cracks or shrinkage that affect its continued use, and no material sticking or oil leakage
Outline Dimensional Drawing

Physical image:

Quick connector plug

Quick connector plug and socket

Typical diagram

Design Specification for Quick Access Box of Generators
1. Box size (maximum size): height 1400 * width 600 * thickness 400mm
2. Configuration inside the box:
Panel socket safety level: IP67 (coupler in plug-in state)
Pluggable connectors (530A): 8 sets
Molded case circuit breaker: rated current 800A, 3-pole, with a breaking capacity of over 50kA.
Power indicator lights: 6
Other accessories: Connection copper bars, transfer switches, etc. meet industry standards.
3. The box is made of stainless copper (304).
4. This box is installed indoors with a height of 0.6 meters above the ground.
Explanation of the structural characteristics of the generator car
1. The fast access box of this generator is configured according to the power of the generator (440KW)
2. Rated circuit: 749A
3. Rated voltage: 400V/230V
4. The generator car is equipped with a main power box
5. Output: 400A * 2 circuits
Typical diagram of quick access box
Explanation:
一、 The input adopts a fast plug input method, and the output uses copper bars connected to cables for output, using 6x60mm copper bars



Copy product links
Long by picture save/share