The European style combined substation complies with the GB/T17467-1998 standard and IEC1330 standard, with flexible and convenient installation, low losses, low noise, and strong resistance to short circuits and overload. Suitable for commercial centers, residential communities, industrial and mining enterprises, hospitals, schools, airports, stations, ports, subways, and other places. There are two types of layouts: eye type font (YBM) and quality type font (YBP).


Product structure characteristics
A. The substation structure is arranged in the shape of "eye" or "product"
B. The product shell material adopts aluminum alloy plate, stainless steel plate, composite plate, glass fiber reinforced cement plate, etc
C. The base of the substation is made of galvanized channel steel or cement, with strong corrosion resistance and sufficient mechanical strength
D. The top cover of the box adopts a double-layer structure, which has good insulation, radiation protection, and ventilation effects
E. Each room of the substation is separated by iron plates to form an independent small room, each room is equipped with lighting facilities. The top of the transformer is equipped with an automatic exhaust device to regulate the temperature of the transformer room
F. The color of the box transformer box is flexible and can coordinate with the surrounding environment
Technical parameters of European combined substation
Project | Unit | High voltage side | Transformer | Low voltage side |
Rated frequency | Hz | 50 | ||
Rated capacity | KVA | 30-2500 | ||
Rated voltage | KV | 10 | 0.4 | |
Rated current | KA | 400\630 | 50-2500 | |
Rated short-time withstand current | KA | 12.5(2s或4s) 16(2s或4s) 20(2s或4s) | 15(1s)、30(1s) 50(1s)、65(1s) | |
Power frequency withstand voltage | KV | 42/48 | ||
Lightning impulse withstand voltage | KV | 75/85 | 75 | |
Tapping range | KV | ±2*2.5% | ||
Protection grade | KA | IP33 | IP23 | IP33 |
Noise level | dB | <50 |
Note: The above parameters are only typical values for reference and can be manufactured according to customer requirements
install
①.acceptance inspection
● When the product arrives, first check whether there is any damage or improper loading and unloading during transportation, and notify our company's Product Technical Service Department of any damage or defects found, so as to handle them properly as soon as possible.
● Before moving the gearbox, tighten or replace any parts or accessories that may have become loose or damaged.
● The product is accompanied by a packing list, certificate of conformity, installation and operation manual, electrical schematic diagram, secondary wiring diagram, outline diagram, installation foundation diagram, instructions for the main equipment used, operating tools (if there are special operating tools), keys (if there are door locks), and spare parts provided according to the agreement. If you have any questions, please contact our product tech
②.Use a crane or elevator to lift the box transformer
Improper use of hooks or cranes may cause serious damage to the box transformer or its accessories, or cause personal injury. There are hooks near the bottom of the box for loading and unloading. The angle between the lifting steel cable and the vertical line during stretching should not exceed 30 °, and it is necessary to support the steel cable with horizontal bars to avoid any deformation caused by box shaped structures or lifting hooks.(See Figure 1)
Warning: Before moving the box, check its weight, as well as the load-bearing capacity and usage status of all hooks or lifting equipment. Do not use worn or damaged steel cables or lifting rings. Do not use lifting equipment with a lifting capacity less than the weight shown on the nameplate of the box transformer.